廣州南洋電纜有限公司——額定電壓1kV及以下架空絕緣電纜
Aerial Insulated cables for rated voltage up to and including 1kV(NAN cable)
一、產(chǎn)品使用范圍及產(chǎn)品標準 Product Application Scope and Standards
本產(chǎn)品適用于交流額定電壓U(Um)為1kV的架空電力線(xiàn)路用銅芯、鋁芯、鋁合金芯耐候型聚氯乙烯、聚乙烯和交聯(lián)聚乙烯絕緣架空電纜。
This product is applicable for AC rated volage U(Um) of 1kV and below aerial power line that needs copper core, aluminum core, aluminum alloy core weather proof PVC, PE and polyethylene (XLPE) insulation aerial cable.
產(chǎn)品標準Product standard: GB/T 14049
二、電纜代號表示方法Cable Code and Description
- 架空電纜系列Series code
- 架空電纜系列 Aerial cable series…………………………………………………JK
- 材料和結構特征代號Materials and structure code
- 銅導體Copper conductor………………………………………………………………T(省略Omission)
- 軟銅導體Soft Copper conductor……………………………………………………TR
- 鋁導體Aluminium conductor………………………………………………………….L
- 鋁合金導體Aluminum alloy conductor……………………………………………LH
- 交聯(lián)聚乙烯絕緣 XLPE insulated………………………………………………………YJ
- 聚乙烯絕緣PE insulated……………….……………..…………………………………..Y
- 聚氯乙烯絕緣PVC insulated……………….……………..…………………………….Y
三、產(chǎn)品型號與主要用途Product type and applications
型號Type | 電纜名稱(chēng)Specification | 主要用途Application |
JKYJ-1 | 銅芯交聯(lián)聚乙烯絕緣架空電纜 | 架空固定敷設、軟銅芯產(chǎn)品用于變壓器引下線(xiàn)電纜假設時(shí),應考慮電纜和樹(shù)木保持一定的距離,電纜運行時(shí)允許電纜和樹(shù)木頻繁接觸 Used for aerial fixed cnonnection and soft copper cable, as down leadi wires of transformer. Keep certain distance between cable and trees when installing, and allow cable and trees contacting frequently when on operation |
Copper conductor XLPE insulated aerial cable |
JKTRYJ-1 | 軟銅芯交聯(lián)聚乙烯絕緣架空電纜 |
Soft copper conductor XLPE insulated aerial cable |
JKLYJ-1 | 鋁芯交聯(lián)聚乙烯絕緣架空電纜 |
Aluminium conductor XLPE insulated aerial cable |
JKLHYJ-1 | 鋁合金交聯(lián)聚乙烯絕緣架空電纜 |
Aluminium-alloyed conductor XLPE insulated aerial cable |
- Aluminium-alloyed conductor light XLPE insulatd aerial cable
- 1kV架空絕緣電纜結構示意圖1kV Aerial insulated cable structrue schematic diagrams
四、使用特性ApplicatIon Features
- 額定電壓U(Um)為1(1.2)KV。Rated voltage U(Um) is 1 (1.2) Kv。
- 電纜可用于單相接地故障時(shí)間每次一般不大于1min的系統,亦可用于最長(cháng)每次不超過(guò)8h,每年累計不超過(guò)125h的系統。
- Cables can be used for those systems of single-phrase ground fault time generally not more than 1 min each time, and maximum not more than 8 hours, accumulatively not more than 125 hours per year.
- 電纜敷設溫度應不低于-20℃。Ambient tmperature should be not lower than -20℃ when cable is installed.
- 短路時(shí)(最長(cháng)持續時(shí)間不超過(guò)5S)交聯(lián)聚乙烯絕緣電纜的最高溫度:電纜的導體溫度250℃。短路時(shí)(最長(cháng)持續時(shí)間不超過(guò)5S)聚氯乙烯絕緣或聚乙烯絕緣電纜的最高溫度:電纜的導體溫度160℃。Maximum conductor temperature is 250℃ when cable is shorted for less than 5 seconds for XLPE insulated Cable. And for PVC or PE insulated Cable, the maximum conductor temperature is 160℃ when cable is shorted for less than 5s。
4、電纜導體的最高長(cháng)期允許工作溫度:(對有承載結構的電纜)交聯(lián)聚乙烯絕緣90℃,而對于聚氯乙烯絕緣或聚烯烴絕緣的架空電纜長(cháng)期允許工作溫度為70℃。For load-bearing XLPE insulated cable maximum rated temperature of conductor is 90℃. And for load-bearing PVC or PE insulated cable maximum rated temperature of conductor is 70℃。
5、電纜敷設后的彎曲半徑應不小于以下規定Minimum bending radius is as follows when cable is installed:
單芯電纜——20(D+d)±5%mm For single-core cable -20(D+d), ±5%mm.
多芯電纜——15(D+d)±5%mm For multi-core cable- 15(D+d), ±5%mm.
(D,d 分別為電纜外徑與導體的標稱(chēng)直徑,單位為:mm)
Note: D denotes the overall diameter of cable, while d means the diameter of the conductor, unit:mullimeter
五、產(chǎn)品規格Product Specification
型號Type | 芯數Number of cores | 標稱(chēng)截面Nominal cross-section mm2 |
JKYJ | 1 | 16~400 |
JKTRYJ | 3 | 25~400 |
JKLYJ | 3+K(A) 或3+K(B) | 25~400其中K25~120 |
JKLHYJ | 3+K(A) 或3+K(B) | 25~400其中K25~120 |
注:1、其中K為承載絞線(xiàn),按工程設計要求,可任選表中規定截面與相應導體截面相匹配,如塔干跨距更大采用外加承載索時(shí),該承載索不包括在電纜結構內。2、其中A表示鋼承載絞線(xiàn),B為鋁合金承載絞線(xiàn)。
Note:1. K denotes load bearing stranded wire, Relevant cross-section conductor can be choosen according to engineering design requirement. If a larger span between poles connected with wxternal load cable, this load bearing wire will not be included in the cable structure. 2. A denotes steel load bearing stranded wire.(B) denotes aluminium-alloyed load bearing stranded wire.